Carrier furnace status code 33: limit circuit fault
What code 33 means
Carrier's service procedures (SP05-59) list code 33 as Limit circuit fault: it indicates that a limit switch or flame rollout switch is open. These switches are safety devices. The furnace shuts the burners down when one of them opens, and it will not fire again until the circuit closes.
On the LED, status codes are two digits. The first digit is the number of short flashes and the second digit is the number of long flashes, so code 33 is three short flashes and then three long flashes.
What the furnace does while code 33 shows
- The blower runs for 4 minutes or until the open switch closes again, whichever is longer. That is why you may hear the fan running with no heat.
- If the switch is open longer than 3 minutes, the code changes to lockout code 13. If it is open less than 3 minutes, code 33 keeps flashing until the blower shuts off.
- A flame rollout switch requires a manual reset (Carrier). Goodman's manual describes the primary limit as automatic-reset and the auxiliary and rollout limits as manual-reset, so which switch tripped matters.
Carrier's check list for code 33
The manufacturer's table says to check for the following. This is the service document's list, written for a technician:
- Dirty filter or restricted duct system
- Proper vent sizing and a restricted vent
- Loose blower wheel
- Excessive wind
- Defective blower motor or capacitor
- Defective switch or connections
- Inadequate combustion air supply
Code 33 across five Carrier and Bryant furnace manuals
We checked the troubleshooting guide in five manufacturer documents. All five print code 33 as LIMIT CIRCUIT FAULT, and all five describe the same blower behavior and the 3-minute change to lockout 13. What differs is which switches are in the circuit and what two-stage boards add:
| Document | Furnace | What code 33 covers | Check list differences |
|---|---|---|---|
| Carrier SP05-59 | 352MAV Series B 2-stage condensing | Limit or flame rollout switch open | Adds excessive wind, vent sizing, restricted vent, defective blower motor or capacitor, inadequate combustion air |
| Carrier 59SC5A-13SI | Comfort 59SC5A single-stage condensing | Limit or flame rollout switch open; rollout switch requires manual reset | Loose blower wheel, defective switch or connections, dirty filter or restricted ducts, improper gas input adjustment, improper limit switch or missing gasket |
| Carrier 59TP6A-10SI | Performance 59TP6A two-stage condensing | Limit or rollout switch open, or high-heat-only operation after 2 successive low-heat limit trips | Adds improper low- or high-heat gas input adjustment. Lockout 13 also follows 10 successive limit trips in high heat |
| Carrier 58SC0A-05SI | Comfort 80 58SC0A / 58SC1A (80% AFUE) | Limit, draft safeguard, flame rollout or blocked vent shutoff switch (if used) open; rollout switch and blocked vent switch require manual reset | Adds defective blower motor or capacitor, inadequate combustion air (rollout open), restricted vent, vent sizing, excessive wind |
| Bryant II926TB-01 | Bryant 926TB two-stage condensing | Same wording as the Carrier two-stage guide, including high-heat-only mode | Same list as 59TP6A |
Two practical points come out of the comparison. First, on an 80% furnace with a chimney (like the 58SC0A), code 33 can be a venting problem, because the draft safeguard switch is wired into the same circuit. Second, on two-stage furnaces a code 33 with the furnace still heating can mean the board has dropped to high heat only after repeated low-heat limit trips, which still points at airflow or gas input.
Why a rollout switch deserves extra respect
Goodman's service manual for its 96% furnaces describes the same family of switches: the primary limit guards against overheating from too little air passing over the heat exchanger, and the rollout limits "guard against burner flames not being properly drawn into the heat exchanger." In other words, an open rollout switch can be a combustion or venting problem, not just a dirty filter. That is the main reason not to keep restarting a furnace that repeats this code.
Only the checks in the list below are homeowner tasks. Everything else on the manufacturer list above needs a technician.
Safe homeowner checks for Carrier furnace code 33
- Check the air filterTurn the thermostat to off. Look at the furnace air filter and replace it if it is clogged. The manufacturer lists a dirty filter first among the causes of an open limit.
- Open supply and return ventsMake sure supply registers and the return grille are open and not blocked by furniture or rugs, because a restricted duct system can overheat the heat exchanger.
- Check outdoor vent and intake pipesFrom outside, look at the furnace vent and combustion-air terminations and clear obvious snow, ice or debris. Do not climb on roofs or open the vent pipes.
- Restart once and watchSet the thermostat to heat. If code 33 or 13 comes back, stop and call a heating technician rather than resetting repeatedly.
Frequently asked questions
Is Carrier code 33 an emergency?
Not by itself. It is a safety shutdown, and the furnace is doing its job by stopping. Treat it as urgent if it repeats, if the code changes to 13, or if you notice a gas smell, soot, a yellow or orange burner flame, or a carbon monoxide alarm.
What is the difference between code 33 and code 13?
Code 33 is the fault while a limit or rollout switch is open for under three minutes. Code 13 is the lockout that follows when the switch has been open longer than three minutes. Carrier says the control resets code 13 automatically after three hours.
Does code 33 mean I need a new furnace?
No. The code points at the safety circuit, and the causes in Carrier's list range from a dirty filter to a loose blower wheel or a failed switch. A technician can find which one it is.
Sources
- SP05-59 Service and Maintenance Procedures: Deluxe 4-Way Multipoise 2-Stage Direct-Vent Condensing Gas Furnace (Carrier (shareddocs.com)) Covers: Carrier 2-stage condensing gas furnaces with the status-code LED control described in the document. Other Carrier, Bryant and Payne boards can use different codes; check the service label on your furnace.
- Installation, Start-up, Operating and Service and Maintenance Instructions 59SC5A-13SI: 59SC5A Single Stage 4-Way Multipoise Condensing Gas Furnace, Series 1 and 2 (Troubleshooting Guide) (Carrier (shareddocs.com)) Covers: Carrier Comfort 59SC5A single-stage condensing furnaces, Series 1 and 2.
- Installation, Start-up, Operating and Service and Maintenance Instructions 59TP6A-10SI (11/18): 59TP6A Two-Stage Variable Speed ECM Multipoise Condensing Gas Furnace (Fig. 72 Troubleshooting Guide) (Carrier (shareddocs.com)) Covers: Carrier Performance 59TP6A two-stage variable-speed condensing furnaces with the amber-LED control.
- Installation, Start-Up, Operating and Service and Maintenance Instructions 58SC0A-05SI (09/21): 58SC0A/58SC1A 80% AFUE Single-Stage Multi-Speed ECM Furnace (Fig. 51 Troubleshooting Guide) (Carrier (shareddocs.com)) Covers: Carrier Comfort 80 58SC0A and 58SC1A (low NOx) non-condensing single-stage furnaces.
- Installation, Start-up, Operating and Service and Maintenance Instructions II926TB-01 (04/19): 926TB Two-Stage Variable-Speed ECM Multipoise Condensing Gas Furnace (Troubleshooting Guide) (Bryant Heating & Cooling Systems (Carrier family; shareddocs.com)) Covers: Bryant 926TB two-stage variable-speed condensing furnaces.
- RS6612023 Service and Troubleshooting: 34.5" Chassis ACVC96/AMVC96/GCVC96/GMVC96 Gas Furnaces (Goodman Manufacturing (Daikin)) Covers: Goodman and Amana 96% two-stage condensing furnaces in the 34.5" chassis.
Safety note: this page is general information drawn from the sources above. Gas, combustion and line-voltage repairs belong to a licensed professional. Your own equipment's label and manual take priority over anything here. Read the full disclaimer.