Trane furnace error codes: blinking lights and S9V2 / S9X display codes
Trane and American Standard furnaces report faults in two different ways depending on the control board. Older Integrated Furnace Controls blink an LED, and the number of flashes between pauses is the code. Current S9V2, S9X1, S9X2 and S9B1 condensing furnaces show a code such as E3.2 or E04 on a small 7-segment display and keep a list of the last six faults. The table keeps the two systems separate, so first look through the sight glass or at the control to see which one you have.
How to read the display
LED-flash boards (18-CH49D1-1): count the flashes in one group before the pause. A slow flash with no call for heat is normal, and a fast flash during a call for heat is also normal. A continuously lit LED means Trane says to replace the IFC, and a continuously dark LED means check power. Because the control is polarity sensitive, the hot leg of the 115 VAC supply must connect to the black field lead; 6 flashes points at reversed polarity, poor grounding or low system voltage.
7-segment boards (S9V2, S9X): the code appears on the display, with an E in front (for example E04, E09 or E3.2). The troubleshooting flow charts in the manuals title the same codes "04 Fault Code", "3.2 Fault Code" and so on. To see the last six faults, press the Menu key until L6F appears, then press Option to step through them. Holding Option for at least 5 seconds inside L6F clears the list; three sets of dashes confirm it. Record the codes before anyone clears them, because a technician will want the history.
Codes in the E2, E3 and E04 to E09 groups describe ignition, pressure switch, limit, flame and condensate problems. E10 and higher on the S9V2 are mostly control-board, blower-motor and personality-module faults that only a technician can address.
Trane / American Standard code table
| Code | Meaning | Applies to | What the document says |
|---|---|---|---|
| Slow flash | Normal: no call for heat | IFC 18-CH49D1-1 (LED flashes) | |
| Fast flash | Normal: call for heat | IFC 18-CH49D1-1 (LED flashes) | |
| Continuous on | Replace the IFC | IFC 18-CH49D1-1 (LED flashes) | |
| Continuous off | Check power | IFC 18-CH49D1-1 (LED flashes) | |
| 2 flashes | System lockout (retries or recycles exceeded) | IFC 18-CH49D1-1 (LED flashes) | |
| 3 flashes | Draft pressure error | IFC 18-CH49D1-1 (LED flashes) | Possible problems: a venting problem, a pressure switch problem or an inducer problem. Full explanation |
| 4 flashes | Open temperature limit circuit | IFC 18-CH49D1-1 (LED flashes) | Full explanation |
| 5 flashes | Flame sensed when no flame should be present | IFC 18-CH49D1-1 (LED flashes) | |
| 6 flashes | 115 volt AC power reversed, poor grounding, or system voltage too low | IFC 18-CH49D1-1 (LED flashes) | |
| 7 flashes | Gas valve circuit error | IFC 18-CH49D1-1 (LED flashes) | |
| 8 flashes | Low flame sense signal | IFC 18-CH49D1-1 (LED flashes) | Full explanation |
| 9 flashes | Check the ignitor circuit and the line N to 24 VAC common voltage (2 volts or less) | IFC 18-CH49D1-1 (LED flashes) | Trane notes a possible grounding problem. |
| E01 | Internal failure of the control board | S9V2 · S9X1 · S9X2 · S9B1 | Replace the IFC. |
| E2.1 | Retry lockout: 3 unsuccessful tries for ignition within one call for heat | S9V2 · S9X1 · S9X2 · S9B1 | Lockout lasts one hour. |
| E2.2 | Recycle lockout: 10 recycles within one call for heat | S9V2 · S9X1 · S9X2 · S9B1 | Lockout lasts one hour. The S9V2 chart describes it as flame sensed and then lost. |
| E2.3 | 1st stage gas valve not energized when it should be, 10 times in the same call | S9V2 · S9X1 · S9X2 · S9B1 | Replace the IFC. |
| E2.4 | Redundant relay (HLO output) not energized when it should be, exceeded 10 times | S9V2 | Replace the IFC. |
| E3.1 | 1st stage pressure switch (PS1) closed when it should be open | S9V2 · S9X1 · S9X2 · S9B1 | Trane: in most cases the pressure switch is not the problem; verify pressure switch wiring and tube routing. |
| E3.2 | 1st stage pressure switch (PS1) open when it should be closed | S9V2 · S9X1 · S9X2 · S9B1 | Trane says PS1 open errors can occasionally occur in wind gusts. The chart checks the inducer, switch orientation, hose and flue piping for obstruction, and vent size. Full explanation |
| E3.3 | 2nd stage pressure switch (PS2) closed when it should be open | S9V2 · S9X2 | |
| E3.4 | 2nd stage pressure switch (PS2) open when it should be closed | S9V2 · S9X2 | |
| E04 | Open limit switch (the S9V2 wiring diagram legend lists open thermal limit, rollout switch or reverse airflow switch) | S9V2 · S9X1 · S9X2 · S9B1 | Limit switches open when an abnormal high temperature is sensed. Trane: never leave these switches jumpered. The chart starts with filters and airflow. |
| E05 | Flame sensed when it should not be | S9V2 · S9X1 · S9X2 · S9B1 | |
| E6.1 | Reversed polarity: incoming high-voltage wiring is reversed | S9V2 · S9X1 · S9X2 · S9B1 | |
| E6.2 | Faulty ground: incoming or chassis ground connection not sensed | S9V2 · S9X1 · S9X2 · S9B1 | |
| E6.3 | Igniter relay fault: relay stuck closed (S9V2 also: igniter circuit open or shorted) | S9V2 · S9X1 · S9X2 · S9B1 | |
| E7.1 | External gas valve circuit error: 24 volts present when it should not be | S9V2 · S9X1 · S9X2 · S9B1 | |
| E7.2 | Redundant HLO relay closed when it should not be | S9V2 | Replace the IFC. |
| E08 | Low flame sense current | S9V2 · S9X1 · S9X2 · S9B1 | The flow charts define it as flame sense current below 0.5 micro-amp DC. |
| E09 | Condensate pressure switch open or inducer limit open | S9V2 · S9X1 · S9X2 · S9B1 | Condensate not draining freely, or an inducer limit trip, which Trane says is normally caused by improper installation or application of the venting system. |
| E10 | Communication error between the inducer and blower motor microprocessors | S9V2 | Replace the IFC. |
| E11 | Internal gas valve relays failed (S9V2 also: 24 VAC sensed at the 2nd stage gas valve) | S9V2 · S9X1 · S9X2 · S9B1 | |
| E12 | Onboard 5 amp fuse open or missing | S9V2 · S9X1 · S9X2 · S9B1 | |
| E13 | Blower motor HP or OEM ID does not match the personality module | S9V2 | |
| E14 | Personality module missing and onboard information cannot be read | S9V2 | The S9X manual says E14 and E18 have been reported on S9X2 furnaces at initial start-up and are not valid errors there. |
| E15 | Personality module and IFC information corrupted | S9V2 | |
| E17 | IFC does not see a return signal from the blower motor | S9V2 | |
| E18 | IFC does not see its own send message | S9V2 | See the E14 note for S9X2. |
Sources: Trane 18-CH49D1-1 'SiNi - IFC Error Codes' table (04/09) for the flash rows; FNR-SVX001C-EN (S9V2) and FNR-SVX002B-EN (S9X1/S9X2/S9B1) Troubleshooting fault-code flow charts and definitions for the E rows.
Which document matches my furnace?
| Column label | Document | Furnaces covered |
|---|---|---|
| IFC 18-CH49D1-1 | Installer's guide 18-CH49D1-1 (04/09), SiNi igniter assembly IGN00117 | Trane and American Standard furnaces with the LED-flash Integrated Furnace Control described in the guide |
| S9V2 | IOM FNR-SVX001C-EN (August 2026) | S9V2B040 through S9V2D120, upflow/horizontal and dedicated downflow, 2-stage variable speed with variable speed inducer |
| S9X1 · S9X2 · S9B1 | IOM FNR-SVX002B-EN (August 2026) | S9X1 and S9B1 single-stage, S9X2 two-stage condensing furnaces with high efficiency motor |
Detailed explanations
- Trane furnace blinking 4 times: open temperature limit circuit
- Trane furnace blinking 3 times: draft pressure error
- Trane furnace blinking 8 times: low flame sense signal
- Trane furnace error E3.2: 1st stage pressure switch open
Sources
- Installer's Guide 18-CH49D1-1: SiNi Igniter Assembly IGN00117 (includes the Integrated Furnace Control error flash codes) (Trane) Covers: Trane and American Standard furnaces using the Integrated Furnace Control (IFC) covered by this installer guide (dated 04/09). Newer boards can differ; check the wiring-diagram label inside your furnace.
- Installation, Operation, and Maintenance FNR-SVX001C-EN (August 2026): S9V2 2-Stage Condensing Variable Speed Furnaces with Variable Speed Draft Inducer (Troubleshooting, Fault Code flow charts) (Trane) Covers: Trane S9V2 upflow/horizontal and dedicated downflow condensing furnaces (S9V2B040 through S9V2D120) with the 7-segment display IFC.
- Installation, Operation, and Maintenance FNR-SVX002B-EN (August 2026): S9X1, S9X2 and S9B1 Single Stage / Two Stage Condensing Furnaces with High Efficiency Motor (Troubleshooting) (Trane) Covers: Trane S9X1 and S9B1 single-stage and S9X2 two-stage condensing furnaces with the 7-segment display IFC.