Carrier and Bryant furnace status codes (5 furnace manuals compared)

Carrier, Bryant and Payne furnaces built on the same family of controls report faults through a status-code LED that you can see through the sight glass in the blower door. We compared the troubleshooting guides in five Carrier and Bryant furnace manuals, from an early-2000s 352MAV to a 2021 58SC0A, and the core codes have kept the same numbers and meanings for two decades. The differences are mostly in the two-stage boards, which add codes 15, 25, 32 and 43.

What this table coversStatus codes from five manufacturer documents: Carrier SP05-59 (352MAV Series B 2-stage condensing), 59SC5A-13SI (Comfort 59SC5A single-stage condensing), 59TP6A-10SI (Performance 59TP6A two-stage condensing), 58SC0A-05SI (Comfort 80 58SC0A/58SC1A single-stage) and Bryant II926TB-01 (926TB two-stage condensing). The Applies to column shows which of those five troubleshooting guides print each code. A code missing from a model's list was not in that guide; it does not prove the code can never appear. Infinity and Evolution communicating systems also report faults as text on the wall control, which this table does not cover. The service label on your blower door is the final authority.

How to read the display

Each status code is a two-digit number. The first digit is the number of short flashes and the second digit is the number of long flashes, so code 33 is three short flashes followed by three long flashes. The 59TP6A and 926TB manuals describe the same rule for their amber LED.

A steady LED means something different from a code. In SP05-59, continuous off means check for 115 VAC at the control and 24 VAC at the transformer, continuous on means the control has 24 VAC power, and rapid flashing means line voltage polarity is reversed. The newer troubleshooting flow charts ask the same three questions (is the LED on, blinking rapidly, or blinking short and long) before you read a code.

Recalling stored codes: on the two-stage 59TP6A and 926TB, technicians disconnect the R thermostat wire, reset power and turn setup switch SW1-1 on; the LED then flashes stored codes in order until code 11. On the 80% 58SC0A red-LED board, the guide says not to remove power or the blower door before recalling the code, and to briefly remove and reconnect one red wire from the draft safeguard switch, or short TEST/TWIN to Com24V. Write the code down before you open the furnace or switch the power off.

Carrier / Bryant code table

CodeMeaningApplies toWhat the document says
11 No previous code 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB Stored codes are erased after 72 hours. On two-stage 59TP6A and 926TB boards they can also be erased manually with setup switch SW1-1; on red-LED boards (SP05-59, 58SC0A) they are erased whenever 115 V or 24 V power is interrupted.
12 Blower on after power up (115 V or 24 V) 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB Normal operation. The 59SC5A, 59TP6A and 58SC0A guides say the blower runs for 90 seconds if the unit is powered up during a call for heat or if the call ends during the blower on-delay.
13 Limit circuit lockout 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB A limit or flame rollout switch was open longer than 3 minutes. Two-stage boards (59TP6A, 926TB) also lock out after 10 successive limit trips in high heat. On the 80% 58SC0A the circuit also includes the draft safeguard switch and, if used, a blocked vent shutoff switch. Auto-resets after 3 hours. Full explanation
14 Ignition lockout 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB The furnace failed to ignite gas and prove flame in 4 attempts. Auto-resets after 3 hours. See code 34. Full explanation
15 Blower motor lockout 59TP6A · Bryant 926TB The blower failed to reach 250 RPM, or failed to communicate within 30 seconds of being turned on, in two successive heating cycles. Auto-resets after 3 hours.
21 Gas heating lockout 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB Turn off power and wait 5 minutes to retry. The guides list a stuck-closed gas valve relay on the control, or a miswire or short to the gas valve wire.
22 Abnormal flame-proving signal 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB Flame is proved while the gas valve is de-energized. The inducer runs until the fault clears. Check for a stuck-open or leaky gas valve.
23 Pressure switch did not open 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB Check for an obstructed pressure tube or a pressure switch stuck closed.
24 Secondary voltage fuse is open 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB Short circuit in the 24 V wiring, including thermostat leads. Technicians disconnect thermostat leads to isolate it.
25 Invalid model selection or setup error 59TP6A · Bryant 926TB Four flashes at power-up mean the model plug PL4 is missing and the control is using the stored model. Continuous flashing can mean a missing plug with no stored model, a thermostat call with SW1-1 or SW1-6 on, twinned furnaces of different models, or the wrong replacement control.
31 Pressure switch did not close or reopened. Two-stage boards: high-heat pressure switch or relay. 59SC5A: LPS or HPS pressure switch 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB Single-stage guides list vent sizing, restricted vent, excessive wind, low inducer voltage, low inlet gas pressure, obstructed or disconnected pressure tubing, a defective inducer or switch, and on condensing models a plugged condensate drain or water in the vent pipe. Two-stage boards refer to code 32.
32 Low-heat pressure switch did not close or reopened 352MAV · 59TP6A · Bryant 926TB If open longer than 5 minutes, the inducer shuts off for 15 minutes before a retry. Check list: vent sizing, restricted vent, excessive wind, low inlet gas pressure, obstructed or disconnected pressure tubing, miswired or defective switches, plugged condensate drain, water in the vent pipe, defective inducer, low inducer voltage. Full explanation
33 Limit circuit fault 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB A limit or flame rollout switch is open (58SC0A adds the draft safeguard and blocked vent switch). On two-stage boards it can also mean high-heat-only operation after 2 successive low-heat limit trips. Blower runs at least 4 minutes; open longer than 3 minutes becomes lockout 13. Flame rollout switch requires a manual reset. Full explanation
34 Ignition proving failure 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB Flame was not sensed during trial for ignition; the control repeats ignition 3 more times before lockout 14. Includes the flame-sensor current check (nominal 4.0 to 6.0 microamps). Full explanation
43 Low-heat pressure switch open while high-heat pressure switch is closed 352MAV · 59TP6A · Bryant 926TB Check for a low-heat switch stuck open, disconnected or obstructed pressure tube, miswired switches, low inlet gas pressure, plugged condensate drain or water in the vent pipe.
45 Control circuitry lockout 352MAV · 59SC5A · 59TP6A · 58SC0A · Bryant 926TB Auto-resets after a 1-hour lockout caused by a flame circuit failure, a gas valve relay stuck open or a software check error. Reset power to clear. Replace the control if the code repeats.

Sources: SP05-59 status code table; 59SC5A-13SI troubleshooting guide p. 83; 59TP6A-10SI Fig. 72 pp. 89-90; 58SC0A-05SI Fig. 51 pp. 36-37; Bryant II926TB-01 troubleshooting guide pp. 88-89. 352MAV = SP05-59. Codes 41 and 42 are referred to in some two-stage guides but are not printed in the pages we read, so they are left out.

Which document matches my furnace?

Column labelDocumentFurnace type
352MAVCarrier SP05-59 Service and Maintenance ProceduresDeluxe 4-way multipoise 2-stage direct-vent condensing (352MAV Series B)
59SC5ACarrier 59SC5A-13SIComfort single-stage 4-way multipoise condensing, Series 1 and 2
59TP6ACarrier 59TP6A-10SI (11/18)Performance two-stage variable-speed ECM condensing
58SC0ACarrier 58SC0A-05SI (09/21)Comfort 80 single-stage multi-speed ECM, 80% AFUE (58SC0A and low-NOx 58SC1A)
Bryant 926TBBryant II926TB-01 (04/19)Two-stage variable-speed ECM multipoise condensing

The model number is on the rating plate inside the furnace. The first five characters (for example 59SC5 or 926TB) identify the family. Bryant and Payne furnaces are built by the same company as Carrier, and the Bryant 926TB guide uses the same code numbers as the Carrier two-stage guide; still check the label on your own blower door.

Most common winter codes Code 33 (limit circuit) and 13 (its lockout) usually point at airflow or venting, so start with the filter and the outdoor vent terminations. Codes 31 and 32 are the pressure-switch family; see our furnace pressure switch guide. Code 34 and its lockout 14 are ignition and flame-sensing problems.

Detailed explanations

SafetyThese tables describe what the manufacturer documents say. Gas, combustion, refrigerant and line-voltage repairs are for licensed professionals. If you smell gas, leave the building and call your gas utility or 911. Safety disclaimer.