Daikin mini-split error codes: FTXC, FTX-B, AXVJU and FTX-N/U series
Daikin wall-mounted and ducted mini-splits report faults as a two-character code on the wireless remote, and most of the codes mean the same thing across series. We read the error tables in four Daikin service manuals that span the FTXC, FTX-B, 19 Series AXVJU and FTX-N/U product lines and merged them into one table, keeping each manual's wording where it differs. These are service manuals, so the full flow charts assume a technician with meters; the code list still tells you which part of the system the unit is complaining about.
How to read the display
Codes starting with A or C are indoor unit faults. Codes starting with E, F, H, J, L or P are outdoor unit faults. U codes are system-level: voltage, communication and installation.
Reading the code on an ARC480-series remote (SiUS091601ED, method 1): hold the TIMER CANCEL button for 5 seconds until 00 appears in the temperature display, then press TIMER CANCEL repeatedly until the unit gives a long beep. The code on the screen at the long beep is the stored error. A short beep or two consecutive beeps mean the code shown is not the one. To return to normal, hold TIMER CANCEL for 5 seconds, or leave the remote alone for 60 seconds. The manual notes that not every code shows with this method and gives a second method for technicians. The FTX-B manual describes the same TIMER CANCEL scroll for its remote.
Every service manual tells technicians to turn the power switch off before connecting or disconnecting connectors, because parts can be damaged. That is one more reason the deeper checks are not for homeowners.
Daikin code table
| Code | Meaning | Applies to | What the document says |
|---|---|---|---|
| 00 | Normal condition | FTXC · FTX-B · AXVJU · FTX-N/U | |
| U0 | Refrigerant shortage (SiUS091601ED); "Insufficient gas" (AXVJU) | AXVJU · FTX-N/U | SiUS091601ED marks U0 as displayed only when the system shuts down. Not listed in the FTXC or FTX-B 4.1 tables. |
| U2 | Low-voltage detection or over-voltage detection ("DC voltage out of range" in AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | |
| U4 | Signal transmission error between indoor unit and outdoor unit ("Communication abnormality" in AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | Supposed causes include power supply voltage problems, a wiring error or broken indoor-outdoor connection wire, a defective indoor or outdoor PCB and a disturbed power supply waveform. Full explanation |
| U5 | Signal transmission error between indoor unit and remote controller | FTX-N/U (FDMQ ducted only) | |
| U7 | Signal transmission error on outdoor unit PCB | FTX-N/U | |
| U8 | Signal transmission error between MAIN/SUB remote controllers | FTX-N/U (FDMQ ducted only) | |
| UA | Installation error between indoor and outdoor unit (FTXC, FTX-B); "Unspecified voltage" (SiUS091601ED); "Installation abnormality" (AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | Points at a mismatched or mis-wired indoor and outdoor combination. Installer issue. |
| A1 | Indoor unit PCB abnormality | FTXC · FTX-B · AXVJU · FTX-N/U | |
| A3 | Drain level control system abnormality | FTX-N/U (FDMQ ducted only) | |
| A5 | Freeze-up protection control (FTXC, FTX-B); "freeze-up protection control / heating peak-cut control" (SiUS091601ED); "antifreeze protection or high pressure control" (AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | |
| A6 | Indoor fan motor (DC motor) or related abnormality | FTXC · FTX-B · AXVJU · FTX-N/U | |
| A8 | Indoor fan PCB abnormality | FTX-N/U (FDMQ ducted only) | |
| AF | Humidifier or related abnormality | FTX-N/U (FDMQ ducted only) | |
| C4 | Indoor heat exchanger thermistor or related abnormality | FTXC · FTX-B · AXVJU · FTX-N/U | |
| C9 | Room temperature thermistor or related abnormality | FTXC · FTX-B · AXVJU · FTX-N/U | |
| CJ | Remote controller thermistor abnormality | FTX-N/U (FDMQ ducted only) | |
| E1 | Outdoor unit PCB abnormality | FTXC · FTX-B · AXVJU · FTX-N/U | |
| E3 | Actuation of high pressure switch | FTXC · FTX-B | |
| E5 | OL activation (compressor overload); the FTXC, FTX-B and SiUS091601ED tables also list a second E5 variant, "OL activation or HPS activation (high pressure switch)"; AXVJU: "Compressor overload" | FTXC · FTX-B · AXVJU · FTX-N/U | |
| E6 | Compressor lock ("Compressor lock / start-up abnormality" in AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | |
| E7 | DC fan lock ("Outdoor fan motor lock" in AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | |
| E8 | Input overcurrent detection ("AC input over current" in AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | |
| EA | Four way valve abnormality | FTXC · FTX-B · AXVJU · FTX-N/U | The four way valve switches the system between heating and cooling, so a fault here matters in winter. |
| F3 | Discharge pipe temperature control ("Discharge pipe overheat" in AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | |
| F6 | High pressure control in cooling ("Heat exchanger overheat" in AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | |
| F8 | System shutdown due to temperature abnormality in the compressor | FTX-N/U | |
| H0 | Compressor sensor system abnormality | FTXC · FTX-B · AXVJU · FTX-N/U | |
| H6 | Position sensor abnormality (compressor start-up failure) | FTXC · FTX-B · AXVJU · FTX-N/U | The compressor failed to start; the system shuts down if the error repeats. See the H6 page. Full explanation |
| H8 | AC current sensor abnormality | AXVJU | |
| H9 | Outdoor temperature thermistor or related abnormality | FTXC · FTX-B · AXVJU · FTX-N/U | |
| J3 | Discharge pipe thermistor or related abnormality | FTXC · FTX-B · AXVJU · FTX-N/U | |
| J6 | Outdoor heat exchanger thermistor or related abnormality | FTXC · FTX-B · AXVJU · FTX-N/U | |
| L3 | Electrical box temperature rise ("compressor off" in AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | |
| L4 | Radiation fin temperature rise ("Heat sink overheat, compressor on" in AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | |
| L5 | Output overcurrent detection ("IPM abnormality" in AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | |
| P4 | Radiation fin thermistor or related abnormality ("Heat sink thermistor abnormality" in AXVJU) | FTXC · FTX-B · AXVJU · FTX-N/U | FTXC and FTX-B manuals: displayed only when the system is shut down. |
Sources: Daikin DAMA-SM-23-020 section 4.1 (FTXC); DAMA-SM-23-006 section 4.1 (FTX-B); AXVJU service manual section 3.3 (AXVJU); SiUS091601ED Part 6 section 4 (FTX-N/U, FVXS, FDMQ). Where manuals word a code differently, the AXVJU or SiUS wording is shown in quotes.
Which manual covers my unit?
| Column label | Daikin document | Indoor / outdoor models covered |
|---|---|---|
| FTXC | Service manual DAMA-SM-23-020 | FTXC-series inverter wall-mounted heat pumps (60 Hz) |
| FTX-B | Service manual DAMA-SM-23-006 (2023) | FTX09/12/18/24BXVJU with RX09/12/18/24BXVJU; cooling-only FTK-BXVJU with RK-BXVJU |
| AXVJU | Service manual, Inverter Wall Mounted Single Split (section 3.3) | FTXB / FTXN 09-24 AXVJU with RXB / RXN; cooling-only FTKB / FTKN with RKB / RKN |
| FTX-N/U | Service manual SiUS091601ED (03/2022) | FTX09/12/15NMVJU(A), FTX18/24UVJU, FVXS09/12/15NVJU, FDMQ12/18/24RVJU with RXL09/12/15QMVJU and RXL18/24UMVJU |
Find the model number on the rating label on the side of the indoor unit or the outdoor unit. If the first letters and the suffix do not match a row above, use the code table in your own unit's manual. For example, the FTX-B manual also prints a longer generic "error code definition" list that includes codes which do not apply to every model, so we only used its section 4.1 table here.
Detailed explanations
- Daikin mini-split error H6: position sensor abnormality (compressor start-up failure)
- Daikin mini-split error U4: signal transmission error between indoor and outdoor unit
Sources
- Service Manual DAMA-SM-23-020: Inverter Split Wall Mounted Heat Pump, FTXC Series (section 4.1 and 4.20) (Daikin) Covers: Daikin FTXC-series inverter wall-mounted heat pumps (60 Hz).
- Service Manual DAMA-SM-23-006: Inverter Split Wall Mounted FTK-B & FTX-B Series (section 4.1 Error Codes and Description, 4.8, 4.20) (Daikin) Covers: Daikin FTX09/12/18/24BXVJU heat pump indoor units with RX09/12/18/24BXVJU outdoor units, and cooling-only FTK-BXVJU / RK-BXVJU pairs (208/230 V, 60 Hz).
- Service Manual: Inverter Wall Mounted Single Split, FTKB/FTKN/FTXB/FTXN-AXVJU (section 3.3 Error code description for Inverter) (Daikin) Covers: Daikin FTXB09-24AXVJU / RXB, FTXN09-24AXVJU / RXN heat pumps and FTKB / FTKN cooling-only pairs (the 19 Series AXVJU wall units).
- Service Manual SiUS091601ED (03/2022): FTX-N/U wall mounted, FVXS-V floor standing and FDMQ-R duct connected with RXL outdoor units (Part 6, 4. Error Codes and Description) (Daikin) Covers: Daikin FTX09/12/15NMVJU(A), FTX18/24UVJU, FVXS09/12/15NVJU and FDMQ12/18/24RVJU indoor units with RXL09/12/15QMVJU and RXL18/24UMVJU outdoor units.