Daikin mini-split error codes: FTXC, FTX-B, AXVJU and FTX-N/U series

Daikin wall-mounted and ducted mini-splits report faults as a two-character code on the wireless remote, and most of the codes mean the same thing across series. We read the error tables in four Daikin service manuals that span the FTXC, FTX-B, 19 Series AXVJU and FTX-N/U product lines and merged them into one table, keeping each manual's wording where it differs. These are service manuals, so the full flow charts assume a technician with meters; the code list still tells you which part of the system the unit is complaining about.

What this table coversError code tables from four Daikin service manuals: DAMA-SM-23-020 (FTXC series), DAMA-SM-23-006 (FTX-B / FTK-B BXVJU), the AXVJU single-split service manual (FTXB / FTXN / FTKB / FTKN AXVJU, section 3.3) and SiUS091601ED (FTX-N/U wall units, FVXS floor units and FDMQ ducted units with RXL outdoor units). The "Applies to" column shows which of those four tables list each code. A code missing from a column was not in that manual's table; that does not prove it can never appear on that unit. Other Daikin lines (FTXS, FTXM Aurora, VRV, Daikin One furnaces) were not used for this table.

How to read the display

Codes starting with A or C are indoor unit faults. Codes starting with E, F, H, J, L or P are outdoor unit faults. U codes are system-level: voltage, communication and installation.

Reading the code on an ARC480-series remote (SiUS091601ED, method 1): hold the TIMER CANCEL button for 5 seconds until 00 appears in the temperature display, then press TIMER CANCEL repeatedly until the unit gives a long beep. The code on the screen at the long beep is the stored error. A short beep or two consecutive beeps mean the code shown is not the one. To return to normal, hold TIMER CANCEL for 5 seconds, or leave the remote alone for 60 seconds. The manual notes that not every code shows with this method and gives a second method for technicians. The FTX-B manual describes the same TIMER CANCEL scroll for its remote.

Every service manual tells technicians to turn the power switch off before connecting or disconnecting connectors, because parts can be damaged. That is one more reason the deeper checks are not for homeowners.

Daikin code table

CodeMeaningApplies toWhat the document says
00 Normal condition FTXC · FTX-B · AXVJU · FTX-N/U
U0 Refrigerant shortage (SiUS091601ED); "Insufficient gas" (AXVJU) AXVJU · FTX-N/U SiUS091601ED marks U0 as displayed only when the system shuts down. Not listed in the FTXC or FTX-B 4.1 tables.
U2 Low-voltage detection or over-voltage detection ("DC voltage out of range" in AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U
U4 Signal transmission error between indoor unit and outdoor unit ("Communication abnormality" in AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U Supposed causes include power supply voltage problems, a wiring error or broken indoor-outdoor connection wire, a defective indoor or outdoor PCB and a disturbed power supply waveform. Full explanation
U5 Signal transmission error between indoor unit and remote controller FTX-N/U (FDMQ ducted only)
U7 Signal transmission error on outdoor unit PCB FTX-N/U
U8 Signal transmission error between MAIN/SUB remote controllers FTX-N/U (FDMQ ducted only)
UA Installation error between indoor and outdoor unit (FTXC, FTX-B); "Unspecified voltage" (SiUS091601ED); "Installation abnormality" (AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U Points at a mismatched or mis-wired indoor and outdoor combination. Installer issue.
A1 Indoor unit PCB abnormality FTXC · FTX-B · AXVJU · FTX-N/U
A3 Drain level control system abnormality FTX-N/U (FDMQ ducted only)
A5 Freeze-up protection control (FTXC, FTX-B); "freeze-up protection control / heating peak-cut control" (SiUS091601ED); "antifreeze protection or high pressure control" (AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U
A6 Indoor fan motor (DC motor) or related abnormality FTXC · FTX-B · AXVJU · FTX-N/U
A8 Indoor fan PCB abnormality FTX-N/U (FDMQ ducted only)
AF Humidifier or related abnormality FTX-N/U (FDMQ ducted only)
C4 Indoor heat exchanger thermistor or related abnormality FTXC · FTX-B · AXVJU · FTX-N/U
C9 Room temperature thermistor or related abnormality FTXC · FTX-B · AXVJU · FTX-N/U
CJ Remote controller thermistor abnormality FTX-N/U (FDMQ ducted only)
E1 Outdoor unit PCB abnormality FTXC · FTX-B · AXVJU · FTX-N/U
E3 Actuation of high pressure switch FTXC · FTX-B
E5 OL activation (compressor overload); the FTXC, FTX-B and SiUS091601ED tables also list a second E5 variant, "OL activation or HPS activation (high pressure switch)"; AXVJU: "Compressor overload" FTXC · FTX-B · AXVJU · FTX-N/U
E6 Compressor lock ("Compressor lock / start-up abnormality" in AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U
E7 DC fan lock ("Outdoor fan motor lock" in AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U
E8 Input overcurrent detection ("AC input over current" in AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U
EA Four way valve abnormality FTXC · FTX-B · AXVJU · FTX-N/U The four way valve switches the system between heating and cooling, so a fault here matters in winter.
F3 Discharge pipe temperature control ("Discharge pipe overheat" in AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U
F6 High pressure control in cooling ("Heat exchanger overheat" in AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U
F8 System shutdown due to temperature abnormality in the compressor FTX-N/U
H0 Compressor sensor system abnormality FTXC · FTX-B · AXVJU · FTX-N/U
H6 Position sensor abnormality (compressor start-up failure) FTXC · FTX-B · AXVJU · FTX-N/U The compressor failed to start; the system shuts down if the error repeats. See the H6 page. Full explanation
H8 AC current sensor abnormality AXVJU
H9 Outdoor temperature thermistor or related abnormality FTXC · FTX-B · AXVJU · FTX-N/U
J3 Discharge pipe thermistor or related abnormality FTXC · FTX-B · AXVJU · FTX-N/U
J6 Outdoor heat exchanger thermistor or related abnormality FTXC · FTX-B · AXVJU · FTX-N/U
L3 Electrical box temperature rise ("compressor off" in AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U
L4 Radiation fin temperature rise ("Heat sink overheat, compressor on" in AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U
L5 Output overcurrent detection ("IPM abnormality" in AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U
P4 Radiation fin thermistor or related abnormality ("Heat sink thermistor abnormality" in AXVJU) FTXC · FTX-B · AXVJU · FTX-N/U FTXC and FTX-B manuals: displayed only when the system is shut down.

Sources: Daikin DAMA-SM-23-020 section 4.1 (FTXC); DAMA-SM-23-006 section 4.1 (FTX-B); AXVJU service manual section 3.3 (AXVJU); SiUS091601ED Part 6 section 4 (FTX-N/U, FVXS, FDMQ). Where manuals word a code differently, the AXVJU or SiUS wording is shown in quotes.

Which manual covers my unit?

Column labelDaikin documentIndoor / outdoor models covered
FTXCService manual DAMA-SM-23-020FTXC-series inverter wall-mounted heat pumps (60 Hz)
FTX-BService manual DAMA-SM-23-006 (2023)FTX09/12/18/24BXVJU with RX09/12/18/24BXVJU; cooling-only FTK-BXVJU with RK-BXVJU
AXVJUService manual, Inverter Wall Mounted Single Split (section 3.3)FTXB / FTXN 09-24 AXVJU with RXB / RXN; cooling-only FTKB / FTKN with RKB / RKN
FTX-N/UService manual SiUS091601ED (03/2022)FTX09/12/15NMVJU(A), FTX18/24UVJU, FVXS09/12/15NVJU, FDMQ12/18/24RVJU with RXL09/12/15QMVJU and RXL18/24UMVJU

Find the model number on the rating label on the side of the indoor unit or the outdoor unit. If the first letters and the suffix do not match a row above, use the code table in your own unit's manual. For example, the FTX-B manual also prints a longer generic "error code definition" list that includes codes which do not apply to every model, so we only used its section 4.1 table here.

Codes that matter most in heating season Going by the meanings in these manuals, the codes that involve the compressor, outdoor fan, reversing valve, power supply or indoor-outdoor communication include U4 (indoor and outdoor units not communicating), H6 (compressor failed to start), E6 (compressor lock), E7 (outdoor DC fan lock), EA (four way valve abnormality) and U2 (supply voltage out of range). A5 is freeze-up or heating peak-cut protection, a protective control rather than a broken part. The safe homeowner checks are the same for all of them: confirm the outdoor unit breaker is on, keep snow and ice clear of the outdoor unit from the outside without touching the fan or wiring, and restart once. Everything inside the cabinets is technician work.

Detailed explanations

SafetyThese tables describe what the manufacturer documents say. Gas, combustion, refrigerant and line-voltage repairs are for licensed professionals. If you smell gas, leave the building and call your gas utility or 911. Safety disclaimer.