Goodman and Amana 96% furnace alarm codes
These Goodman and Amana furnaces show a three-character code on a seven-segment display on the integrated control board, which you can see through the blower door window. The manual calls the table the Alarm Code Definition Table.
How to read the display
The manual says an active alarm is reported in the status menu "starting with E and following with the appropriate two digit alarm code." That is why almost every code on the display begins with E. An alarm called "E0" appears as EE0 on the three-character display, and an alarm called "d0" appears as Ed0. The table below lists the three characters you will actually see.
Lockout means the furnace could not light after three attempts in a single call for heat. The manual says the control resets itself after a one-hour lockout, and that it can also be reset by interrupting 115-volt power to the furnace or by lowering the thermostat so there is no call for heat for a short time (the manual gives 1 to 20 seconds). Do not keep resetting a furnace that locks out repeatedly. That is the furnace telling you something is wrong.
Goodman / Amana code table
| Code | Meaning | What the document says |
|---|---|---|
| EEE | Internal control fault | |
| EE0 | Lockout due to excessive retries or recycles | The control tried to light three times in one call for heat. It resets itself after one hour, or by interrupting power or cycling the thermostat. A technician should find why it would not light. Full explanation |
| EE1 | Low-stage pressure switch stuck closed at the beginning of heating | The manual lists a sticking switch or a short in the pressure switch wiring as causes. |
| EE2 | Low-stage pressure switch open | The inducer runs but the switch does not close. The manual lists a blocked or pinched hose, blocked flue or inlet pipe, blocked drain, weak inducer or a bad switch. Full explanation |
| EE3 | Open high limit switch | The primary limit circuit is open and the blower runs. Check filters and ductwork first. Full explanation |
| EE4 | Flame detected when no flame should be present | |
| EE5 | Open fuse | |
| EE6 | Low flame signal | |
| EE7 | Igniter fault or improper grounding | |
| EE8 | High-stage pressure switch stuck closed at start of heating cycle | |
| EE9 | High-stage pressure switch open | |
| EEA | Reversed line polarity | |
| EEb | Internal gas valve error | |
| EEC | External gas valve error | |
| EEd | Auxiliary limit switch open | See the guidance on the open-limit page. The manual says to determine why the auxiliary limit opened before resetting it. Full explanation |
| EEF | Condensate switch open | |
| E10 | Grounding fault | |
| E11 | Rollout switch open | The manual says that if a rollout switch has tripped it is important to find out why. Full explanation |
| E12 | Redundant relay open | |
| E13 | Redundant relay stuck closed | |
| Ed0 | Data not yet on network | |
| Ed1 | Invalid data on network | |
| Ed4 | Invalid external shared data | |
| Ed5 | Invalid downloaded firmware | |
| Ed6 | Unrecognized data ID | |
| Eb0 | Blower motor not running | |
| Eb1 | Blower communication alarm | |
| Eb2 | Blower motor HP/ID mismatch | |
| Eb3 | Blower motor operating in power, temperature or speed limit | |
| Eb4 | Blower motor current trip or lost rotor | |
| Eb5 | Blower motor locked rotor | |
| Eb6 | Over/under voltage trip or over temperature trip | |
| Eb7 | Incomplete parameters sent to motor | |
| Eb9 | Inadequate airflow | |
| EC1 | Network communication alarm | |
| EC2 | E-Module network communication alarm | |
| EC3 | Bluetooth module network communication alarm |
Source: Goodman RS6612023, Alarm Code Definition Table (page 57), read from the printed table. Actions are given only where the manual describes the condition elsewhere.
Detailed explanations
- Goodman and Amana furnace code EE0: lockout due to excessive retries or recycles
- Goodman and Amana furnace code EE2: low-stage pressure switch open
- Goodman and Amana furnace code EE3: open high limit switch (also EEd and E11)
Sources
- RS6612023 Service and Troubleshooting: 34.5" Chassis ACVC96/AMVC96/GCVC96/GMVC96 Gas Furnaces (Goodman Manufacturing (Daikin)) Covers: Goodman and Amana 96% two-stage condensing furnaces in the 34.5" chassis.