Lennox furnace diagnostic codes (SL280DFV)
Lennox furnaces with this integrated control show their status and faults on a seven-segment display on the control board. Codes that start with E are faults, and the manual says what clears each one.
How to read the display
Normal operation is shown with letters rather than codes. A blinking decimal point is idle mode. "H" is gas heat, "h" is heat pump stage, "C" is cooling, "d" is dehumidification and "dF" is defrost mode. A fault is shown as a letter E followed by three digits, such as E250.
In the Lennox table, the E1xx codes are mostly power, ground and communication faults, and the E2xx codes are furnace operation faults such as limits, pressure switches, flame and the blower. A soft lockout lasts one hour, and the manual says that for the codes below it "clears when heat call finishes successfully."
Lennox code table
| Code | Meaning | What the document says |
|---|---|---|
| E000 | No error in memory | |
| E105 | Device communication problem, no other devices on RS BUS | The manual says to separate high-voltage power from the RSBus wiring and check for miswired or loose connections between the thermostat, indoor and outdoor units. The fault clears after communication is restored. |
| E110 | Low line voltage | Voltage is lower than the nameplate rating. Check power line voltage and correct. The alarm clears 5 seconds after the fault recovers. |
| E111 | Listed in the table as "Low line voltage"; the action given is to correct reversed line power wiring | The system resumes normal operation 5 seconds after the fault recovers. |
| E112 | Ground not detected | The system shuts down. Provide proper earth ground. |
| E113 | High line voltage | Voltage is higher than the nameplate rating. Provide power voltage within the proper range. |
| E115 | Low 24-volt power | The range is 18 to 30 volts. The manual says to check for power-robbing equipment and that a larger VA transformer may be required. |
| E117 | Poor ground detected (warning only) | Provide proper grounding for the unit. |
| E124 | Communicating thermostat signal missing for more than 3 minutes | The equipment lost communication with the thermostat. Check the four wiring connections and cycle power at the thermostat. |
| E125 | Control failed self-check, internal error | Hardware problem on the control. Cycle power. Replace if the problem is persistent and prevents service. |
| E200 | Hard lockout: rollout circuit open or previously open | Correct the cause of the rollout trip, or replace the flame rollout switch. Test furnace operation. |
| E201 | Indoor blower communication failure | Lost communication with the indoor blower motor. The manual lists motor not powered or loose wiring. |
| E204 | Gas valve miswired | Check gas valve operation and wiring. |
| E205 | Gas valve control relay contact shorted | Check wiring on the control and gas valve. If wiring is correct, replace the control. |
| E206 | Gas valve second-stage relay failure | The furnace will operate on first stage for the rest of the heating demand. |
| E207 | Hot surface igniter sensed open | Measure igniter resistance and replace it if it is open or outside the specified range. |
| E223 | Low pressure switch failed open | Check the pressure at which the low pressure switch closes, then inspect the vent and combustion air inducer for correct operation and restriction. Full explanation |
| E224 | Low pressure switch failed closed | Check whether the switch is stuck closed on a heat call longer than 150 seconds. |
| E225 | High pressure switch failed open | Check the pressure at which the high pressure switch closes, and inspect the vent and inducer. |
| E226 | High pressure switch failed closed | |
| E227 | Low pressure switch open during trial for ignition or run mode | Full explanation |
| E228 | Combustion air inducer calibration failure | Unable to perform pressure switch calibration. Check the vent system and pressure switch wiring. |
| E229 | Ignition on high fire | The control switched to high-fire ignition because the low-fire pressure switch did not close in the allowed time. The manual says no action is needed. |
| E240 | Low flame current, run mode | Check flame sensor microamps. Clean or replace the sensor and check the ground. The alert clears after the heat call. |
| E241 | Flame sensed out of sequence, flame still present | Shut off gas. Check for a gas valve leak. |
| E250 | Limit switch circuit open | If the limit does not close within 3 minutes, the furnace goes into a 1-hour soft lockout. Full explanation |
| E252 | Discharge air temperature too high (gas heat only) | Check temperature rise, airflow and input rate. |
| E270 | Soft lockout: exceeded maximum number of retries, no flame current sensed | Check for proper gas flow, that the igniter is lighting the burner, and flame sensor current. Full explanation |
| E271 | Soft lockout: last retry failed because the pressure switch opened | Inspect the vent and combustion air inducer for correct operation and restriction. Full explanation |
| E272 | Soft lockout: last recycle was due to the pressure switch opening | Full explanation |
| E273 | Soft lockout: last recycle was due to flame failure | Check flame sensor microamps. Clean or replace the sensor. Full explanation |
| E274 | Soft lockout: last recycle failed because the limit circuit opened, or stayed open more than 3 minutes | 1-hour soft lockout. Check firing rate, airflow and blockage. Full explanation |
| E275 | Soft lockout: flame sensed out of sequence | Shut off gas and check for a gas valve leak. 1-hour soft lockout. |
| E290 | Igniter circuit fault | Measure igniter resistance. Replace if open or out of specification. 1-hour soft lockout. |
| E292 | Indoor blower motor unable to start (obstructed wheel or seized bearings) | 1-hour soft lockout. Clears after the blower successfully starts. |
| E295 | Indoor blower motor temperature too high | The motor tripped on its internal protector. Check bearings and amps. |
Source: Lennox 508246-01 (04/2024), Integrated Control Diagnostic Codes. This is a selection of the heating-related codes in that table, not the full list.
Detailed explanations
- Lennox furnace code E250: limit switch circuit open (and E274)
- Lennox furnace code E270: soft lockout, exceeded maximum retries, no flame sensed
- Lennox furnace code E223: low pressure switch failed open (also E227, E271, E272)
Sources
- Installation Instructions 508246-01 (04/2024): SL280DFV Elite Series gas furnace, Integrated Control Diagnostic Codes (Lennox) Covers: Lennox SL280DFV variable-capacity condensing gas furnaces with the integrated control described in the document. Other Lennox furnace lines can use different code sets.