Mitsubishi MSZ/MSY-GL blinking light codes

On these Mitsubishi indoor units the OPERATION INDICATOR lamp blinks when the unit detects a fault. The number of flashes in each cycle tells you which area has the problem.

What this table coversIndicator-lamp patterns from the Mitsubishi service manual OBH732C for the MSZ-GL06 to GL24 and MSY-GL09 to GL24 wall-mounted indoor units. Other Mitsubishi series (GX, FH, multi-zone) have their own tables.

How to read the display

Count the flashes of the upper lamp of the OPERATION INDICATOR. A steady rapid blink (on 0.5 seconds, off 0.5 seconds) is one pattern. The numbered patterns flash that many times and then stay off for 2.5 seconds before repeating. The manual says to check at least two consecutive cycles to be sure of the count.

The manual also describes a "failure mode recall" function, run with the remote and the emergency operation switch, that reports the stored fault with a different numbering (1, 2, 3, 11 and 12 flashes for the indoor unit). Those numbers do not match this table, and the manual warns of exactly that. The table below is the one for the lamp as it normally blinks.

Mitsubishi code table

CodeMeaningWhat the document says
Rapid blink (0.5 s on, 0.5 s off) Miswiring or serial signal problem between indoor and outdoor unit The condition is that the serial signal from the outdoor unit is not received for 6 minutes. Full explanation
2 flashes Indoor coil or room temperature thermistor short or open circuit Full explanation
3 flashes Indoor fan motor: no rotational frequency feedback signal during indoor fan operation Full explanation
4 flashes Indoor unit control system: cannot properly read data in the nonvolatile memory of the indoor control board The remedy is to replace the indoor electronic control board.
5 flashes Outdoor power system: compressor stopped three times consecutively within 1 minute of startup from overcurrent or startup failure protection Indoor and outdoor units do not operate. Check the stop valve (technician work).
6 flashes Outdoor thermistors short or open during compressor operation
7 flashes Outdoor control system: cannot properly read data in the nonvolatile memory of the inverter or outdoor control board
14 flashes or more Other outdoor unit abnormality The manual lists checking the stop valve and the 4-way valve, and using the outdoor unit failure mode recall for details.

Source: Mitsubishi OBH732C, 9-4 Troubleshooting check table (indicator lamp column) and 9-3 flow chart.

Detailed explanations

SafetyThese tables describe what the manufacturer documents say. Gas, combustion, refrigerant and line-voltage repairs are for licensed professionals. If you smell gas, leave the building and call your gas utility or 911. Safety disclaimer.