Furnace pressure switch error: what the code means and what to check
What the pressure switch does
Before a modern gas furnace lights its burners, a small fan called the draft inducer starts and pulls air through the heat exchanger and out the vent. The pressure switch is connected to that system by a rubber hose and closes only when the inducer creates enough suction. If the switch does not close, the control will not open the gas valve. That is a safety feature: it keeps the burners off when combustion gases may not be venting properly.
Pressure switch codes by brand
| Brand and series | Code | Meaning in the manufacturer document | Document |
|---|---|---|---|
| Carrier / Bryant two-stage (352MAV, 59TP6A, 926TB) | 32 | Low-heat pressure switch did not close or reopened | SP05-59, 59TP6A-10SI, II926TB-01 |
| Carrier / Bryant two-stage | 31 | High-heat pressure switch or relay did not close or reopened | Same |
| Carrier / Bryant two-stage | 43 | Low-heat pressure switch open while high-heat pressure switch is closed | Same |
| Carrier single-stage (59SC5A, 58SC0A) | 31 | Pressure switch (LPS or HPS on 59SC5A) did not close or reopened | 59SC5A-13SI, 58SC0A-05SI |
| Carrier / Bryant (all five) | 23 | Pressure switch did not open | All five Carrier and Bryant guides |
| Trane / American Standard LED boards | 3 flashes | Draft pressure error | 18-CH49D1-1 |
| Trane S9V2, S9X1, S9X2, S9B1 | E3.2 (E3.4 for 2nd stage) | Pressure switch open when it should be closed | FNR-SVX001C-EN, FNR-SVX002B-EN |
| Trane S9V2, S9X | E3.1 (E3.3 for 2nd stage) | Pressure switch closed when it should be open | Same |
| Goodman / Amana 96% (34.5" chassis) | EE2 / EE9 | Low-stage / high-stage pressure switch open | RS6612023 |
| Goodman / Amana 96% | EE1 / EE8 | Low-stage / high-stage pressure switch stuck closed | RS6612023 |
| Lennox SL280DFV | E223 / E225 | Low / high pressure switch failed open | 508246-01 |
| Lennox SL280DFV | E227, E271, E272 | Low pressure switch open during ignition or run; soft lockouts after the pressure switch opened | 508246-01 |
| Rheem / Ruud 801T, 80MSX | 57 / 55 | Pressure switch stuck open / stuck closed | 92-24161-144-08 |
| York TM9V | 3 red / 2 red | Pressure switch contacts open when they must be closed / closed when they must be open | 5750149-UIM-I-0423 |
| York TM9V | 6 red, 13 red | Pressure switch opened four times in one call for heat (1-hour lockout); high-fire pressure switch open | Same |
Most of these tables come from documents for specific series. If your furnace is a different series, use the label inside your furnace door or its manual; codes can change between boards even within one brand.
Open versus closed: two different problems
Switch open when it should be closed (Carrier 31/32, Trane E3.2, Goodman EE2, Lennox E223, Rheem 57, York 3 red) is by far the more common pattern. The inducer is running, but the switch is not seeing enough suction. Switch closed when it should be open (Carrier 23, Trane E3.1, Goodman EE1, Rheem 55, York 2 red) is checked before the inducer starts. Carrier lists an obstructed pressure tube or a switch stuck closed; Goodman lists a sticking switch or a short in the switch wiring; York lists a faulty switch or miswiring.
What the manuals say causes "switch open"
- Vent or intake blocked or restricted. Carrier lists a restricted vent and proper vent sizing; Goodman a blocked flue or inlet pipe; York a blocked vent pipe; Trane flue piping obstruction and incorrect vent size; Lennox says to inspect the vent for restriction. In winter, snow drifts and ice at the outdoor pipe ends are the version of this a homeowner can see.
- Wind. Carrier lists excessive wind. Trane says pressure switch open errors can occasionally happen in wind gusts.
- Condensate (high-efficiency furnaces). Carrier lists a plugged condensate drain and water in the vent piping (possible sagging pipe); Goodman lists a blocked drain. Water that cannot drain backs up and blocks the pressure signal.
- The hose. Carrier: disconnected or obstructed pressure tubing. Goodman: a blocked or pinched hose. Trane: verify the hose and tube routing.
- The inducer. Carrier: defective inducer motor or low inducer voltage. Goodman: a weak inducer. York: a faulty inducer. Lennox: inspect the combustion air inducer for correct operation.
- The switch itself. Every brand lists a defective switch, but Trane makes a point of saying that in most cases the pressure switch is not the problem. Replacing it without finding the cause often brings the code back.
Safe checks for a homeowner
- Write down the code exactly, and the furnace model number from the rating plate, before you turn anything off. Some controls, for example Carrier red-LED boards, erase stored codes when power is interrupted.
- Go outside and find where the furnace pipes leave the house (usually two plastic pipes on a high-efficiency furnace, or a metal flue through the roof on an 80% furnace). Clear snow, ice, leaves or nests you can reach safely from the ground. Do not climb onto the roof or take pipes apart.
- Indoors, look without touching anything electrical: is the rubber hose from the pressure switch visibly off its fitting, or is there water in a clear condensate tube or pooling under the furnace? Note what you see for the technician.
- If it is very windy, note it. Wind is a listed cause.
- Restart once by turning the thermostat off for a few minutes and back to heat. If the code returns, call a licensed heating technician.
When to stop and call
- The code repeats after the vent terminations are clear.
- The furnace goes into lockout (for example Carrier 13/14 type lockouts, York 6 red, Lennox soft lockouts).
- You see water leaking from the furnace or in the vent pipe, or a sagging vent pipe.
- You hear the inducer motor grinding or not starting.
Safe homeowner checks for a furnace pressure switch code
- Record the code and modelWrite down the flash pattern or display code and the furnace model number before cutting power.
- Clear the outdoor vent and intakeFrom the ground, clear snow, ice and debris from the furnace exhaust and intake terminations.
- Look for obvious hose or water problemsWithout touching wiring, look for a disconnected pressure switch hose or water pooling or trapped in tubes, and note it.
- Restart onceTurn the thermostat off for a few minutes, then back to heat. If the code returns, call a technician.
Frequently asked questions
Can a dirty filter cause a pressure switch error?
None of the pressure switch check lists in these documents names the air filter. A dirty filter is listed for limit codes instead (for example Carrier 33, Trane 4 flashes or E04). Change it anyway if it is dirty, but look at the vent and condensate for a pressure switch code.
Why does my furnace pressure switch error happen only when it is very cold or windy?
Wind is a listed cause in the Carrier and Trane documents, and snow or ice at the vent terminations restricts the vent. Both are worse in winter storms.
Is it the pressure switch or the inducer?
A technician tells them apart by measuring the suction at the switch and comparing it with the value printed on the switch label, which is the step in Trane's flow chart. If suction is low, the problem is the vent, hose, drain or inducer, not the switch.
Sources
- SP05-59 Service and Maintenance Procedures: Deluxe 4-Way Multipoise 2-Stage Direct-Vent Condensing Gas Furnace (Carrier (shareddocs.com)) Covers: Carrier 2-stage condensing gas furnaces with the status-code LED control described in the document. Other Carrier, Bryant and Payne boards can use different codes; check the service label on your furnace.
- Installation, Start-up, Operating and Service and Maintenance Instructions 59SC5A-13SI: 59SC5A Single Stage 4-Way Multipoise Condensing Gas Furnace, Series 1 and 2 (Troubleshooting Guide) (Carrier (shareddocs.com)) Covers: Carrier Comfort 59SC5A single-stage condensing furnaces, Series 1 and 2.
- Installation, Start-up, Operating and Service and Maintenance Instructions 59TP6A-10SI (11/18): 59TP6A Two-Stage Variable Speed ECM Multipoise Condensing Gas Furnace (Fig. 72 Troubleshooting Guide) (Carrier (shareddocs.com)) Covers: Carrier Performance 59TP6A two-stage variable-speed condensing furnaces with the amber-LED control.
- Installation, Start-Up, Operating and Service and Maintenance Instructions 58SC0A-05SI (09/21): 58SC0A/58SC1A 80% AFUE Single-Stage Multi-Speed ECM Furnace (Fig. 51 Troubleshooting Guide) (Carrier (shareddocs.com)) Covers: Carrier Comfort 80 58SC0A and 58SC1A (low NOx) non-condensing single-stage furnaces.
- Installation, Start-up, Operating and Service and Maintenance Instructions II926TB-01 (04/19): 926TB Two-Stage Variable-Speed ECM Multipoise Condensing Gas Furnace (Troubleshooting Guide) (Bryant Heating & Cooling Systems (Carrier family; shareddocs.com)) Covers: Bryant 926TB two-stage variable-speed condensing furnaces.
- Installer's Guide 18-CH49D1-1: SiNi Igniter Assembly IGN00117 (includes the Integrated Furnace Control error flash codes) (Trane) Covers: Trane and American Standard furnaces using the Integrated Furnace Control (IFC) covered by this installer guide (dated 04/09). Newer boards can differ; check the wiring-diagram label inside your furnace.
- Installation, Operation, and Maintenance FNR-SVX001C-EN (August 2026): S9V2 2-Stage Condensing Variable Speed Furnaces with Variable Speed Draft Inducer (Troubleshooting, Fault Code flow charts) (Trane) Covers: Trane S9V2 upflow/horizontal and dedicated downflow condensing furnaces (S9V2B040 through S9V2D120) with the 7-segment display IFC.
- Installation, Operation, and Maintenance FNR-SVX002B-EN (August 2026): S9X1, S9X2 and S9B1 Single Stage / Two Stage Condensing Furnaces with High Efficiency Motor (Troubleshooting) (Trane) Covers: Trane S9X1 and S9B1 single-stage and S9X2 two-stage condensing furnaces with the 7-segment display IFC.
- RS6612023 Service and Troubleshooting: 34.5" Chassis ACVC96/AMVC96/GCVC96/GMVC96 Gas Furnaces (Goodman Manufacturing (Daikin)) Covers: Goodman and Amana 96% two-stage condensing furnaces in the 34.5" chassis.
- Installation Instructions 508246-01 (04/2024): SL280DFV Elite Series gas furnace, Integrated Control Diagnostic Codes (Lennox) Covers: Lennox SL280DFV variable-capacity condensing gas furnaces with the integrated control described in the document. Other Lennox furnace lines can use different code sets.
- Installation Instructions 92-24161-144-08: Upflow/Horizontal Single Stage Gas Furnaces, (-)801T and (-)(-)80MSX series, section 14 Diagnostics and Fault Codes (Rheem (Rheem and Ruud brands)) Covers: Rheem and Ruud (-)801T upflow/horizontal single-stage furnaces and (-)(-)80MSX upflow/horizontal furnaces with the seven-segment display control. Other Rheem and Ruud furnace series can use different controls.
- Installation Manual 5750149-UIM-I-0423: Two-Stage Variable Speed ECM Residential Gas Furnaces, TM9V*C series (96% AFUE), Furnace control diagnostics (Johnson Controls (York)) Covers: York TM9V*C two-stage variable-speed 96% furnaces. Other York and Coleman furnace series use different boards and flash codes; check the label on your furnace.
Safety note: this page is general information drawn from the sources above. Gas, combustion and line-voltage repairs belong to a licensed professional. Your own equipment's label and manual take priority over anything here. Read the full disclaimer.