Rheem and Ruud furnace fault codes (801T series)
Furnaces with this control have a seven-segment display on the board. It shows a single character in normal operation and a two-digit number when there is a fault.
How to read the display
With no faults, the display reads 0 in standby. During operation it shows a letter: C for cooling or heat pump operation, F for continuous fan and H for gas heating. A fault is shown as a two-digit number.
Each two-digit number is shown one digit at a time. The first digit is displayed for one second, then the second digit for one second, then there is a half-second pause and the cycle repeats. When two faults are present, the display alternates between them with a short bar between. Rheem says that after four failed ignitions the display alternates 10 and 11, and that after five flame losses in a row it alternates 10 and 13. Code 10 means a one-hour soft lockout.
Rheem / Ruud code table
| Code | Meaning | What the document says |
|---|---|---|
| 0 | Standby | |
| C | Compressor on (cooling or heat-pump heat) | |
| H | Gas heat on | |
| F | Continuous fan on | |
| 10 | One-hour lockout (soft lockout) | Alternates with the code for the fault that caused the lockout, such as 11, 13, 14 or 61. The lockout resets automatically after one hour. Full explanation |
| 11 | Failed ignition | Four failed ignition trials in a row cause a one-hour lockout, shown as 10 and 11. Full explanation |
| 12 | Low flame sense | |
| 13 | Flame lost | Flame lost five times in one heat call causes a one-hour lockout, shown as 10 and 13. |
| 14 | Unexpected flame | The control enters a one-hour lockout, shown as 14 and 10. |
| 20 | Twinning fault | |
| 22 | Main limit or HALC open | If the main limit stays open more than 150 seconds during a gas heat call, the display alternates 61 and 22. Full explanation |
| 26 | Line and neutral reversed | |
| 33 | MRLC (manual reset limit control, also called rollout) open | |
| 55 | Pressure switch stuck closed when it should be open | |
| 57 | Pressure switch stuck open when it should be closed | If the low pressure switch does not close after 60 seconds of inducer operation, the control starts a five-minute soft lockout. |
| 61 | Blower fault: blower unable to run | Declared when the main limit has been open for more than 150 seconds. Full explanation |
| 93 | Internal control fault | A hard lockout that cannot be cleared by cycling the heat call. |
Source: Rheem installation instructions 92-24161-144-08, Diagnostics and Fault Codes.
Detailed explanations
- Rheem and Ruud furnace display alternating 10 and 11: one-hour lockout after failed ignition
- Rheem and Ruud furnace codes 22 and 61: main limit open and blower fault
Sources
- Installation Instructions 92-24161-144-08: Upflow/Horizontal Single Stage Gas Furnaces, (-)801T and (-)(-)80MSX series, section 14 Diagnostics and Fault Codes (Rheem (Rheem and Ruud brands)) Covers: Rheem and Ruud (-)801T upflow/horizontal single-stage furnaces and (-)(-)80MSX upflow/horizontal furnaces with the seven-segment display control. Other Rheem and Ruud furnace series can use different controls.