Rheem and Ruud furnace display alternating 10 and 11: one-hour lockout after failed ignition

Short answerOn a Rheem or Ruud (-)801T furnace, a display that alternates 10 and 11 means the control tried to light four times in a row, failed, and started a one-hour soft lockout. Rheem says the lockout resets automatically after one hour, or sooner if power is cycled or the heat call is ended for more than 2 and less than 20 seconds.

What 10 and 11 mean together

Rheem's installation instructions for the (-)801T series list code 10 as a one-hour lockout and code 11 as failed ignition. When a failed ignition has occurred four times in a row, the control enters a one-hour lockout and displays 10 and 11 alternately. Code 10 on its own tells you only that the furnace is in a soft lockout. The second code tells you what caused it.

Each two-digit code is shown one digit at a time. The first digit appears for one second, then the second digit for one second, then a half-second pause, and then the cycle repeats. So 1 then 0 is code 10, and 1 then 1 is code 11.

All the situations that cause a "10" lockout

Rheem says a one-hour soft lockout starts when any of these happens, and the display alternates 10 with the code for the cause:

Display alternatesCause (per Rheem)
10 and 11Flame has not been detected after four ignition trials.
10 and 13Flame was lost five times in one heat call.
14 and 10Undesired (unexpected) flame was detected. The hour starts after flame is no longer detected.
61 and 10A dead blower was detected: the main limit circuit was open for more than 150 seconds.
10 and another codeVoltage was unexpectedly detected on the gas valve circuit and went away when the inducer shut off.

How a lockout resets

Rheem says all lockout conditions can be cleared immediately once the original fault is cleared and power to the unit is cycled off and back on. For a soft lockout only, the lockout can also be cleared if the heat call is cycled off for more than 2 seconds but less than 20 seconds. Otherwise the soft lockout resets automatically after one hour. The control will not start a heat cycle during any lockout.

Rheem's document does not list the physical causes of a failed ignition in this section. Other manufacturers' manuals list the usual suspects: no gas, a weak igniter, a dirty or coated flame sensor, a pressure switch problem and blocked venting. For comparison, see Goodman EE0 and Lennox E270, which describe the same situation on different controls. Finding the cause on a Rheem furnace is technician work.

Safety Never jumper, bypass or tape over a limit, rollout or pressure switch. If you smell gas, leave the house and call your gas utility from outside. If a carbon monoxide alarm sounds, get everyone outside and call 911.

Safe homeowner checks for Rheem or Ruud furnace codes 10 and 11

  1. Check that gas is availableSee whether another gas appliance such as a stove or water heater is working. If you smell gas, leave the house and call your gas utility from outside.
  2. Clear outdoor vent and intake pipesFrom the ground, clear snow, ice or debris from the plastic vent and combustion air terminations. Do not climb on a roof or take pipes apart.
  3. Reset once with the thermostatSet the thermostat below room temperature for about 10 seconds (more than 2, less than 20), then back to heat. This is the soft-lockout reset Rheem describes.
  4. Stop if it returnsIf the display goes back to 10 and 11, turn the thermostat off and call a heating technician. Repeated attempts will not fix a gas, igniter or flame sensing problem.

Frequently asked questions

How long does the Rheem furnace stay locked out?

One hour for a soft lockout. It resets automatically after that, or sooner if you cycle power or end the heat call for more than 2 and less than 20 seconds.

What does 12 mean on a Rheem furnace?

Rheem lists code 12 as low flame sense, which is the control reporting a weak flame signal. It is separate from 11 (failed ignition) and 13 (flame lost).

What is a hard lockout on this furnace?

Rheem describes it as code 93 (internal control fault) or a dead blower declared four times in one heat call (code 61). A 93 hard lockout cannot be reset by cycling the heat call.

Sources

Safety note: this page is general information drawn from the sources above. Gas, combustion and line-voltage repairs belong to a licensed professional. Your own equipment's label and manual take priority over anything here. Read the full disclaimer.